Operation and performance |
Fluid types |
Liquids: acoustically conductive fluids, including most clean liquids, and many liquids with small amounts of entrained solids or gas bubbles |
Flow Measurement |
Patented Correlation Transit-Time™ model |
Pipe Sizes |
0.75 in to 300 in (20 mm to 7.5 m) |
Pipe Wall Thickness |
Up to 4 in (100 mm); consult factory for other wall thicknesses |
Pipe Material |
All metals and most plastics. Consult RS Hydro for concrete, composite materials, and highly corroded or lined pipes. |
Accuracy |
±1% of reading: >=2 in/50 mm, >1 ft/s (0.3 m/s)
±2% of reading: <2 in/50 mm, >1 ft/s (0.3 m/s)
±0.5% in field calibration possible
Installation assumes a fully developed, symmetrical flow profile (typically 10 diameters upstream and 5 diameters downstream of straight pipe run). Final installation accuracy is a function of multiple factors including pipe centricity, installation accuracy, and others. |
Repeatability |
±0.2% of reading typical |
Range (Bidirectional) |
0.1 to 65.6 ft/s (0.03 to 20 m/s) |
Measurement Cycle |
3 Hz typical (Adjustable to 10 Hz) |
Measurement Parameters |
Velocity, Volumetric, Mass, Energy, Total Flow |
Channels |
1, 2, or 3 channels |
Optional PC Software |
Vitality™ PC Software |
XMT1000 Flow Transmitter |
Enclosure |
Epoxy-coated aluminum or stainless steel NEMX 4X / IP66 & IP67 rating |
Specifications |
- Weight: 10 lb. (4.5 kg
- Size (D x H x W): 8.40 in. x 6.42 in. x 5.87 in. (213.4 mm x 163.1 mm x 149.1 mm)
- Mounting: 2 in. pipe or wall mount
|
Hazardous Area Rating |
US/CAN: Class I, Division 1, Groups B, C, D;
Class I, Zone 1, Ex d IIC T6;
Class I, Division 2, Groups A, B, C, D;
Class I, Zone 2, Ex nA IIC
ATEX/IECEx: Ex d IIC T6 FISCO outputs
Ta = -40° C to +60° C, Type 4X |
Temperature Range |
- Operating: -40°F to 149°F (-40°C to +65°C)*
- Storage: –67°F to 167°F (–55°C to 75°C)
*Maximum ambient temperature is 60°C (140°F) when
foundation fieldbus option selected. |
Display |
128 x 64 mono-color LCD display, configurable for single or dual measurement parameters. |
Keypad |
Built-in magnetic, six-button, lockable keypad |
Standard Inputs/Outputs |
- One 4 to 20 mA isolated output, 600 Ohm maximum load
- One additional output may be configured as either a pulse or frequency output.
|
Digital Communication |
- Standard: RS485/Modbus
- Optional: HART® 7.0 protocol, with 4 dynamic variables, includes one additional 4 to 20 mA analog output
- Optional: Foundation Fieldbus® FISCO, LAS capable with 5 AI blocks and a PID block.
|
Power Supplies |
Universal 100-240 VAC 50/60 Hz ±10% or 12 to 28 VDC |
Power Consumption |
15W maximum, Typically <7W
Inrush current: 25 A maximum @ 100 µs
15 A maximum @ 1 ms |