The 2-track SITRANS FUS380 flowmeter can be supplied as a battery or mains-powered unit and is designed to measure water flow in local networks, boiler stations, substations, chiller plants and other general water applications. The type-approved flowmeter version is named SITRANS FUE380. Technically, the SITRANS FUS380 and SITRANS FUE380 are completely identical, with the only difference being the calibration limit and the type approval for custody transfer.
The 2-track design of the FUS 380 ensures maximum accuracy under short inlet conditions. The flowmeter consists of a flow sensor pipe, 4 transducers/transducer cables and a SITRANS FUS080 transmitter. When ordering a compact version the transducer cables are pre-mounted and ready for installation. Compact mounting is only possible up to 120 °C (248 °F). The sensor must be isolated to protect the transmitter from heat. The unit is available in a compact or a remote version with up to 30 meter distance from flowmeter to transmitter.
The flowmeter digital output is often used as input for an energy meter or as input for digital systems for remote reading. SITRANS FUS380 has two digital output functions that can be individually selected, and optional MODBUS RTU communication modules. Pulse output rate is defined when ordering. If the flowmeter forms part of an energy meter system for custody transfer, no further approvals are needed, except possible local approvals on the flowmeter
The FUS380 is available in an IP67/NEMA 4X/6 enclosure.The main application for the transmitter is measurement of water flow in heat meter system or chilled water.
Manufactured by: Siemens-Milltronics
Model: SITRANS FUS380 Two Track Flowmeter
Heating plants
Boiler stations
Local networks
Sub-stations
Chiller plants
Other general water applications
Measuring Range | Qp 15 to 36000 m3/h (depends on size) |
Nominal Size | From DN 50 to DN 1200 (2" to 48") |
Accuracy | ±0.5% of flow rate |
Operational Pressure | Pressure rate max. PN 40 |
Operation Temperature | From 0 to 60 °C (32 to 140 °F) |
Medium Temperature | From 2 to 200 °C (35.6 to 392 °F) Bronze: Up to 150 °C (302 °F) |
Design | 2-track sensor with flanges and integrated transducers |
Material | Carbon steel Bronze (only DN 50 to 80) |