The HOBO Occupancy & Light data logger monitors room occupancy and indoor light changes to identify occupancy patterns and determine energy usage and potential savings. The HOBO UX90-005 Room Occupancy/Light Data Logger is available in a standard 128 KB memory model (UX90-005) capable of 84,650 measurements and an expanded 512KB memory version (UX90-005M) capable of over 346,795 measurements.
Manufactured by: Onset
Model: HOBO Occupancy/Light (5m Range) Data Logger
Light on/off
Occupancy
Occupancy Sensor | |
Detection Range | |
UX90-005x | maximum 5 m (15.4 ft); |
UX90-006x | maximum 12 m (39.4 ft) |
Detection Performance | |
UX90-005x | 94° (±47°) Horizontal; 82° (±41°) Vertical (see Figure A in manual) |
UX90-006x | 102° (±51°) Horizontal; 92° (±46°) Vertical (see Figure B in manual) |
Detection Zones | |
UX90-005x | 64 (see Figure A in manual) |
UX90-006x | 92 (see Figure B in manual) |
Light Sensor | |
Light threshold | > 65 lux |
Light type | LED, CFL, fluorescent, HID, incandescent, natural |
Logger | |
Time accuracy | ±1 minute per month at 25°C (77°F) (see Plot A in manual) |
Battery life | 1 year typical use |
Memory | |
UX90-005/-006 | 128 KB (84,650 measurements, maximum) |
UX90-005M/-006M | 512 KB (346,795 measurements, maximum) |
Download type | USB 2.0 interface |
Download time | 10 seconds for 128 KB; 30 seconds for 512 KB |
Logger Operating Range | |
Logging | -20° to 70°C (-4° to 158°F); 0 to 95% RH (non-condensing) |
Launch/readout | 0° to 50°C (32° to 122°F) per USB specification |
Occupancy sensor range | 20° to 60°C (-4° to 140°F); 15 to 85% RH (non-condensing) |
LCD | LCD is visible from: 0° to 50°C (32° to 122°F); the LCD may react slowly or go blank in temperatures outside this range |
Size | |
UX90-005x | 3.66 x 8.48 x 2.36 cm (1.44 x 3.34 x 0.93 in.) |
UX90-006x | 3.66 x 8.48 x 2.87 cm (1.44 x 3.34 x 1.13 in.) |
Weight | 30 g (1.06 oz) |
Environmental rating | IP50 |
The CE Marking identifies this product as complying with all relevant directives in the European Union (EU) |