Siemens HydroRanger Plus (Discontinued)

  • Easily Customised To Meet Specific Application Needs Enables measurement in a multitude of applications from flow rate in a narrow flume to volume in a ferric chloride storage bank
  • Optional Submergence Sheilds Ensures consistent operation in wet wells where transducers are likely to be submerged ensuring accuracy
Product Options

Overview

PRODUCT DISCONTINUED- REPLACED BY THE HydroRanger 200 .

The Siemens HydroRanger Plus is an ultrasonic level transmitter for control of wet wells and reservoir pump operations, differential control, and open channel flow monitoring, using energy-saving algorithms.

The HydroRanger Plus is effective in wet wells, weirs and flumes where foam and turbulence are typical operating conditions. It can be customized to meet your specific application needs from measuring flow rate in a narrow flume to volume in a ferric chloride storage bank.

The ultrasonic level transmitter consists of the electronics housed in a wall-mounted enclosure and a hermetically sealed, corrosion-resistant Echomax transducer. These components can be separated by up to 365 m (1200 ft).

Optional submergence shields ensure consistent operation in wet wells where the transducer may be submerged during flooding from rainfall or a power outage. Milltronics patented detection software can differentiate between a submerged condition and a high level.

  • Outputs for alarms, chart recorders, controllers and integration of existing systems
  • Monitors wetwells, weirs and flumes
  • Energy saving function with built-in real-time clock
  • Special control mode to reduce grease rings and other deposits
  • Integral temperature compensation
  • Pump performance monitoring
  • Energy management
  • System monitoring and network analysis

Manufactured by: Siemens-Milltronics
Model: Siemens HydroRanger Plus (Discontinued)

Services offered for this product

  • Sales
  • Rental
  • Installation
  • Calibration
  • Maintenance
  • IoT Cloud Compatible

Applications

Wet wells & Pump Control
Flumes and weirs

Specification

Mode of Operation
Measuring Principle Ultrasonic level measurement
Measuring Range 0.3 ... 15 m (1 ... 50 ft)
Measuring Points 1 or 2
Output
Ultrasonic Transducer 44 kHz
Relays 5 alarm/control relays, 1 SPDT
Form C per relay, rated 5 A at
250 V AC, resistive load
mA Output 0/4 ... 20 mA, optically isolated
- Max. Load 1 kΩ
- Resolution 0.1 % of 20 mA
Accuracy
Error in Measurement 0.25% of range or 6 mm (0.24"),
whichever is greater
Resolution 0.1% of measuring range or
2 mm (0.08"), whichever is
greater1)
Temperature Compensation -50 ... +150 °C (-58 ... +302°F)
- Integral temperature sensor
- External TS-3 temperature
sensor (optional)
- Programmable fixed temperature
Rated Operating Conditions - Ambient Conditions
Ambient Temperature for Enclosure -20 ... +50 °C (-4 ... +122 °F)
Design
Rack Mount DIN 3 HU/14 pitch, 4 rail plug-in unit suitable for standard 84 pitch (19") rack
Panel Mount Suitable for standard panel
cutout DIN 43700, 72 x 144 mm,
100 mm center height
Degree of Protection (wall mount) IP65/NEMA 4X/Type 4X
Weight (rack and panel mount) 0.87 kg (1.9 lbs)
Weight (wall mount) 1.5 kg (3.3 lbs)
Material (enclosure) Polyester/polycarbonate alloy
Electrical Connection Commercially available copper
conductor according to local
requirements, rated 250 V/5 A
Ultrasonic Transducer Cable Extension RG 62-A/U coaxial cable with
low capacitance
mA Output Signal 2-core copper conductor,
twisted, shielded,
0.5 ... 0.75 mm2 (22 ... 18 AWG),
Belden 8760 or equivalent is
acceptable
Power Supply 100/115/200/230 V AC, ±15%,
50/60 Hz, 15 VA and/or
9 ... 30 V DC, 8 W
Ultrasonic Transducer Compatible transducers: ST-H
and Echomax series XPS-10/10F, XPS 15/15F, XCT-8, XCT-12 and XRS-5
Display and Controls
Rack and Panel Mount 75 x 20 mm (3 x 0.8") LCD
(selectable backlighting)
Wall Mount 100 x 40 mm (4 x 1.5") multifield
LCD, backlit
Programming Removable programmer or optional Dolphin Plus
Memory EEPROM (non-volatile), no
backup battery required
Certificates and Approvals CE2), FM, CSAUS/C, C-TICK
1)The measuring range corresponds to the distance from the zero point to the sensor face, plus any range extension.
2)EMC certificate available on request

Accessories

Related products