The Sitrans LUT400 series are a range of compact, single-point, ultrasonic level controllers suitable for long-range continuous level or volume measurement of liquids, slurries and solids. They are also suitable for open channel flow measurement.
There are three versions available to choose from depending on the application, functionality and level of performance required:
- The SITRANS LUT420 provides level or volume measurement of liquids, slurries and solids. It also benefits from basic pump control functions and logging facilities.
- The SITRANS LUT430 features the same functions as the LUT420 but also benefits from a full suite of advanced pump control and alarm functionality, open channel flow measurement, and basic flow logging.
- The SITRANS LUT440 provides high accuracy OCM. It has all the features of the LUT430, plus a full suite of advanced control functionality, enhanced flow logging capabilities and the industry's best accuracy (+/- 1mm within 3 m).
MCERTS
The SITRANS LUT430 and LUT440 are now MCERTS certified meeting the Environment Agency's performance requirements. View downloads for certificate.
Manufactured by: Siemens-Milltronics Model: SITRANS LUT400 Ultrasonic Level Controller Series
Services offered for this product
- Sales
- Rental
- Installation
- Calibration
- Maintenance
Applications
- Wet wells
- Flumes/weirs
- Reservoirs
- Chemical storage
- Liquid storage
- Crusher bins
- Dry solids storage
Mode of Operation |
Ultrasonic level, volume, pump,
and open channel flow |
Measuring range |
0.3 - 60 m (1 - 196 ft), transducer dependent |
Input |
Discrete |
0 ... 50 V DC switching level
Logical 0 = < 10 V DC
Logical 1 = 10 ... 50 V DC
Max. 3 mA |
Output |
Transducer frequency |
10 ... 52 kHz |
Ultrasonic transducer |
Compatible transducers: All
EchoMax and ST-H series transducers |
Relays |
• 1 SPDT Form C, NO or NC relay,
rated 1A at 250 V AC, non-inductive and 3A at 30 V DC
• 2 SPST Form A, NO relays, rated
5A at 250 V AC, non-inductive and
3 A at 30 V DC |
mA output |
4 - 20 mA, isolated |
• Max. load |
600 Ω max. in ACTIVE mode,
750 Ω max. in PASSIVE mode |
• Resolution |
0.1 % of range |
Accuracy |
Error in measurement |
• Standard operation: ± 1 mm
(0.04 inch) plus 0.17 % of measured distance
• High accuracy OCM: ± 1 mm
(0.04 inch), within 3 m (9.84 ft)
range |
Resolution |
• Standard operation: 0.1 % of
range or 2 mm (0.08 inch), whichever is greater
• High accuracy OCM: 0.6 mm
(0.02 inch), within 3 m (9.84 ft)
range |
Temperature compensation |
-40 ... +150 °C (-40 ... +300 °F)
• Integral temperature sensor in
transducer
• External TS-3 temperature
sensor (optional)
• Programmable fixed
temperature values |
Rated operating conditions |
Installation conditions |
|
• Location |
Indoor/outdoor |
• Installation category |
II |
• Pollution degree |
4 |
Ambient conditions |
|
• Ambient temperature (enclosure) |
-20 - +50 °C (-4 - +122 °F) |
Design |
Weight |
|
• Enclosure with display lid: |
1.3 kg (2.87 lbs) |
• Enclosure with blank lid: |
1.2 kg (2.65 lbs) |
Material (enclosure) |
Polycarbonate |
Degree of protection |
|
• Enclosure with display or blank lid: |
IP65/Type 4X/NEMA 4X |
• Enclosure with blank lid and
knock-out removed: |
IP20 |
• Remote display lid: |
IP65/Type 3/NEMA 3 |
Cable |
Transducer and mA output signal |
• Transducer, mA output:
2 copper conductors, twisted,
with foil shield/drain wire, 300 V
0.5 - 0.75 mm² (22 - 18 AWG)
• Relay/power to be copper
conductors per local
requirements to meet 250 V
5 A contact rating |
Max. separation between
transducer and transceiver |
365 m (1 200 ft) |
Displays and controls |
60 x 40 mm (2.36 x 1.57 inch)
removable LCD, 240 x 160 pixels
resolution, operational up to 5 m
from enclosure base |
Programming |
|
• Primary |
4 Local push buttons |
• Secondary |
• PC running SIMATIC PDM
• PC running Emerson AMS Device
Manager
• PC running a web browser
• PC running a Field Device Tool
(FDT)
• Field Communicator 375/475
(FC375/FC475) |
Memory |
• 512 kB flash EPROM
• 1.5 MB flash for data logging |
Power supply |
AC version |
100 ... 230 V AC ± 15 %,
50/60 Hz, 36 VA
Fuse: 5 x 20 mm, Slow Blow,
0.25 A, 250 V |
DC version |
10...32 V DC, 10 W
Fuse: 5 x 20 mm, Slow Blow,
1.6 A, 125 V |
Certificates and approvals |
General |
CSAUS/C, CE, FM, UL listed,
C-TICK |
Hazardous |
|
• Non-incendive
(Canada) |
CSAUS/C Class I, Div. 2, Groups A, B,
C, D; Class II, Div. 2, Groups F, G;
Class III |
Files and software available to download:
Siemens LUT440 Installation for V-Notch level and flow measurement